Evaluation of Level Transmitter Performance Through Calibration Data in the Instrument Maintenance Unit of PLTGU Cilego
DOI:
https://doi.org/10.61132/ijmecie.v2i4.363Keywords:
Calibration Data, Instrument Maintenance, Level Transmitter, Performance Evaluation, Preven-tive CalibrationAbstract
This study evaluates the consistency of transmitter level performance through calibration data obtained from the Instrumentation Maintenance Unit of the Cilegon PLTGU. The purpose of this study is to determine the accuracy, linearity, and stability of transmitter output against standard reference values. Qualitative methods were used, including direct observation, interviews, and literature studies to support the analysis of calibration procedures. Calibration data from the Masoneilan 12420-51 and Yokogawa EJA210E transmitters were analyzed using a comparative approach between normal and abnormal calibration results. Classification was based on the difference between the actual output and the 4–20 mA standard signal, with a tolerance limit of ±0.25% in accordance with ISA and IEC calibration standards. The results of the study show that the Level-3 Deaerator Storage Tank transmitter operates within the normal range, with excellent linearity and accuracy, while the Flash ST Tank Level transmitter shows minor deviations outside the tolerance limit, categorized as abnormal. These deviations suggest the potential for drift or zero shift influenced by environmental factors and aging. This study concludes that periodic calibration is necessary to maintain tranmitter performance reliability and ensure accurate signal transmission in the automatic control system at the Cilegon PLTGU facility.
References
Antariksa, A. A., & Sinaga, N. (2023). Optimasi performa gas turbine generator (GTG) unit PLTGU Cilegon PGU melalui analisis performa pada variabel beban berbeda dan strategi peningkatan efisiensi PT. PLN Indonesia Power Cilegon PGU. Jurnal Teknik Mesin S-1, 11(2), 39–48.
Budi Purwaka, P., Taufik, M., Lahtiani, S., & Jamaludin, J. (2022). Uji banding laboratorium kalibrasi: Kalibrasi sound level meter dengan artefak Rion NL-10A. Jurnal Ecolab, 16(1), 13–22. https://doi.org/10.20886/jklh.2022.16.1.13-22
Darmawan, N., & Yuwono, T. (2019). Effect of increasing sea water temperature on performance of steam turbine of Muara Tawar Power Plant. IPTEK: The Journal for Technology and Science, 30(2), 60–67. https://doi.org/10.12962/j20882033.v30i2.4994
Fatimah, L. A., & Hidayat, R. (2024). Analisis hasil studi kasus kalibrasi pressure transmitter dengan metode zero calibration. ELECTRON: Jurnal Ilmiah Teknik Elektro, 5(1), 21–29. https://doi.org/10.33019/electron.v5i1.109
Hasibuan, M. P., Azmi, R., Arjuna, D. B., & Rahayu, S. U. (2023). Analisis pengukuran temperatur udara dengan metode observasi. Jurnal Garuda Pengabdian Kepada Masyarakat, 1(1), 8–15. https://doi.org/10.55537/gabdimas.v1i1.582
Jesse, A., Firdaus, A., Pramono, D., Purnomo, W., Studi, P., Informasi, S., Komputer, F. I., & Universitas Brawijaya. (2020). Pengembangan sistem informasi UPT kalibrasi Dinas Kesehatan Kabupaten Malang berbasis web. Jurnal Sistem dan Teknologi Informasi (JUSTSI), 1(1), 23–34. https://doi.org/10.25126/justsi.v1i1.3
Komalasar, A., & Saragih, Y. (2024). Sistem kontrol temperature transmitter pada reaktor AP-545 di PT Sintas Kurama Per-dana. Aisyah Journal of Informatics and Electrical Engineering, 6(1), 27–34. https://doi.org/10.30604/jti.v6i1.161
Noor, N., & Sari, K. (2020). Rancang bangun media pengenalan huruf. Jurnal Teknologi Informasi, 14(2), 161–170. https://doi.org/10.47111/jti.v14i2.1214
Pamor, G. (2021). Pengukuran adalah kegiatan membandingkan suatu besaran yang diukur dengan alat ukur., 4(2), 187–198.
Pilendia, D. (2020). Pemanfaatan Adobe Flash sebagai dasar pengembangan bahan ajar fisika: Studi literatur. Jurnal Tunas Pendidikan, 2(2), 1–10. https://doi.org/10.52060/pgsd.v2i2.255
Prasetio, D., Sahbana, M. A., & Hermawan, D. (2021). Optimasi LP (low pressure) auxiliary steam pada desalination plant untuk meningkatkan produksi steam turbine PLTGU Grati. Journal Mechanical and Manufacture Technology (JMMT), 2(2), 52–64. https://doi.org/10.35891/jmmt.v2i2.2701
Singh, Y., & Raghuwanshi, S. K. (2019). Design and development of a novel level transmitter utilizing lithium niobate (LiNbO3) Mach–Zehnder modulator for hazardous regions. Optik, 181, 748–759. https://doi.org/10.1016/j.ijleo.2018.12.086
Syahputra, A., & Muhaimin, A. (2022). Analisa kalibrasi level transmitter dengan metode uji lineritas arus pada plant kontrol level. Jurnal Tektro, 6(1), 5–12.
Waruwu, M. (2024). Pendekatan penelitian kualitatif: Konsep, prosedur, kelebihan dan peran di bidang pendidikan. Afeksi: Jurnal Penelitian dan Evaluasi Pendidikan, 5(2), 198–211. https://doi.org/10.59698/afeksi.v5i2.236
Wicaksono, D. B. (2023). Rancang bangun sistem kendali nilai klorin pada kandungan air laut menggunakan metode fuzzy logic. Journal of Computer Electronic and Telecommunication, 4(1). https://doi.org/10.52435/complete.v4i1.217